Energy Storage with Lead–Acid Batteries
The battery was comprised of 12 parallel strings of 118, 5-cell, lead–acid modules; thus, each string consisted of 590 cells, the battery consisted of 1416 modules or 7080 cells, and the nominal battery voltage was 1180 V. The battery used a flooded, copper-stretch-metal technology; the latter feature enhanced the negative-plate …